DIMENSIONS: 300x210x65 mm
WEIGHT: 1650 g
DISPLAY: 5.7¡± 320x240 graphic colour LCD
OPERATING SYSTEM: LINUX
LANGUAGES: Italian, English, French, Spanish, and German.
CASE: Hard case
MEMORY: type I COMPACT FLASH up to 4Gbyte (512Mbyte supplied).
PROTECTION RATING: IP20
ALTITUDE: up to 3000 m
TEMPERATURE: from 0¡Æ to 60¡Æ C
RELATIVE HUMIDITY: 80% for temperatures up to 31¡ÆC with linear decrease to 50% at the temperature of 40¡ÆC
INPUT CHANNELS
SAMPLING
TOTAL NUMBER OF CHANNEL: 7
AD RESOLUTION: 14bit
SAMPLING FREQUENCY: 22.4 KSample/second at 50Hz
26.88 KSample/second at 60Hz
VOLTAGES
NUMBER OF CHANNELS: 3 (independent)
MAX VRMS BETWEEN CHANNELS: 1000 VACRMS
NUMBER OF SCALES: 2 (can be set up on set-up page)
VRMS THAT CAN BE MEASURED AT TERMINALS: 1.5¢¬500 VACRMS or 2¢¬700VDC low scale
3¢¬1000 VACRMS or 5 ¢¬1400VDC high scale
PRECISION (RMS VALUES): <¡¾0.2% r.d.g ¡¾ 0.05% f.s.
MAX MEASURABLE Vpeak: 1400 V
PRECISION (peak VALUES): <¡¾5% r.d.g ¡¾ 1% f.s.
MAX VOLTAGE APPLICABLE AT THE TERMINALS: 600V CAT III pollution degree 2
CURRENTS
NUMBER OF CHANNELS: 4 (3 + 1 auxiliary)
INPUT IMPEDANCE: 10KW
MAX INPUT VOLTAGE: 5Vpp
TYPE OF CLAMPS THAT CAN BE USED: Flexible clamps without amplifier (except auxiliary channel)
Traditional clamps (output 0 ¢¬ 1VAC/DC)
Flexible clamps with amplifier (output 0 ¢¬ 1VAC)
CLAMP CONNECTOR: Hypertronics DO1PB306NT
MEASURABLE IRMS: Flex clamps supplied 5 ¢¬ 1400ARMS
Other clamps (output 0 ¢¬ 1VAC/DC)
0.3% * ¢¬ 140% of the nominal current of the clamp used.
PRECISION (RMS VALUES): <¡¾0.2% r.d.g ¡¾ 0.05% f.s. + clamp error
PRECISION (peak VALUES): <¡¾5% r.d.g ¡¾ 1% f.s. + clamp error
FREQUENCY From 40 to 80 Hz (fundamental frequency)
PRECISION <¡¾0.01 Hz
REFERENCE STANDARDS
SAFETY EN 61010-1
Safety requirements for electrical equipment for measurement, control and laboratory use
EMC EN61326; EN61326/A1/A2/A3
Electrical equipment for measurement, control and laboratory use EMC requirements
MEASUREMENT EN 61000-4-30
Testing and measurement techniques
Power quality measurement method
EN 61000-4-7
Testing and measurement techniques
General guide on harmonics and interharmonics
measurements
ACCESSORIES TECHNICAL DATA
FLEXIBLE CLAMPS
OUTPUT VOLTAGE: 39.1 ¥ìV/A at 50 Hz
LINEARITY: <0.3%
DISPLACEMENT AT 50 Hz: <0.5¡Æ
PROTECTION RATING: IP65
SELF-EXTINGUISHING UL94-V0
ELECTRICAL SAFETY EN 61010-1 and EN 61010-2-32
CAT III 1000VRMS – double insulation
LENGTH OF CONNECTION CABLE: 200 cm
IDENTIFICATION: by purple, green and blue wire markers
VOLTAGE CONNECTION CABLES
COLOURS: red, yellow, blue
(the black plug identifies the neutral)
LENGTH: 200 cm
INSULATION: CAT III 600V
POWER SUPPLY
INPUT VOLTAGE 100 ¢¬ 240 VAC
INPUT FREQUENCY 50-60Hz
OUTPUT VOLTAGE 12 VDC
POWER >40W
BATTERIES
BATTERIES: 10 rechargeable NiMh type AA 2300mAh batteries
BATTERY-OPERATION TIME: about 2 hours with backlight ON
>3 hours with backlight OFF
BATTERY CHARGER: Internal
MAXIMUM BATTERY RECHARGE DURATION: about 10 hours, with instrument on
about 20 hours, with instrument off
|